Exhaust system
1. Local exhaust In order to prevent harmful gases, vapors and dust scattered in the workshop, the main use of local exhaust system from the source directly discharged from the outside. Part of the exhaust system by the local exhaust hood (dust cover), ventilation pipes, fans, dust or harmful gas purification equipment and exhaust devices and other components.
The local exhaust hood (suction hood) is a key component in the local exhaust system. The exhaust cabinet is a common part of the closed exhaust device. When the resulting harmful gas, steam or dust of the workpiece is large and can not be processed in the exhaust cabinet, you can use one side open, the other side of the closed side of the exhaust hood, or parties can not be closed side of the exhaust (Groove width> 0.7m) and blow-out slot side ventilation (groove width> = 0.7m), the side of the exhaust, = 2.0m) in various forms. The exhaust air volume should be greater than the air flow.
In order to obtain good local discharge of dust, harmful gas or steam effect, regardless of the use of which exhaust hood, should consider the following requirements: ① should be harmful substances as close as possible, exhaust hood should be as close as possible Harmful exhaust material should be consistent with the direction of the escape of harmful substances; ③ exhaust hood should be arranged so that the air does not flow through the workers of the respiratory zone; ④ exhaust The device should not be located near the doors and windows, so as to avoid the air into the air to interfere with the exhaust effect; ⑤ exhaust hood to have a certain control wind speed. The proper air flow is caused by the point of harm (ie, the point of control) at the point of the farthest away from the hood, thereby drawing the harmful substance into the hood. The air flow velocity at the control point is called the control wind speed (also called the suction speed). That is, the speed should be greater than the speed of harmful objects to escape and prevent the lateral flow of the speed of interference in order to effectively smoke the harmful substances into the closed equipment. When the side of the exhaust hood, the removal of harmful substances, not only to be closer to the hood from the a hazardous substances control, but also must be far point b of the harmful substances at the control of its Control the wind speed should be Vx, in order to receive a good exhaust effect. The size of the control wind speed should be related to the size of the toxicant, the size of the dust particle size, the general control of the wind speed of 0.7-1.0m / s, dust control wind speed of 1-1.5m / s.
2. Overall exhaust is generally installed in the external wall of a certain number of exhaust fan, relying on the exhaust air to form a negative pressure inside the room, the outdoor fresh air through the doors and windows into the room, so that the entire workshop ventilation and make the harmful gas concentration dilute to meet Hygienic standards.
The total ventilation capacity can be calculated as follows: L = M / (S-S0)
M is the amount of harmful gas emissions (mg / h); S is the maximum allowable concentration of harmful gases (mg / m3); S. For the concentration of harmful gases in the intake air.
When several kinds of solvent vapor or several kinds of irritating gas are simultaneously distributed in the air, the ventilation volume should be calculated according to the sum of the amount of air required to dilute to the maximum allowable concentration respectively. When other harmful substances are dispersed in the air at the same time, the ventilation is calculated only for the most harmful substances in the air.